BS 8491:2008(R2015)大直径电力电缆着火完整性测试
BS 8491:2008(R2015)大直径电力电缆着火完整性测试,BS6387一般针对直径在20mm电缆的完整性能测试,线缆耐火测试是指发生火焰燃烧时,电线电缆产品能够在外部火焰依然燃烧的情况下正常运行一定时间,保持线路完整性和设备正常运转的电线电缆产品。南京睿督公司咨询电话:025-8658 3475。

BS 8491:2008(R2015) 火灾完整性测试
BS 8491:2008(R2015) Method for assessment of fire integrity of large diameter power cables for use as components for smoke and heat control systems and certain other active fire safety systems
BS 8491:2008(R2015) 用于烟和热控制系统及特定的其他仍在继续的火灾安全系统部件的大直径电力电缆着火完整性的评估方法

BS 8491:2008(R2015)标准适用范围
The Standard- BS 8491:2008(R2015) describes a method for assessment of the fire integrity of large diameter power cable for use as components for smoke and heat control systems as given in BS 7346-6, and certain other active fire safety systems. It is applicable to cables of rated voltage not exceeding 600/1000V and of overall diameter greater than 20mm

电线电缆耐火最高等级为BS6387CWZ等级,BS6387-2013在火焰条件下电缆保持线路完整性的耐火试验方法(BS6387-2013 Test method for resistance to fire of cables required to maintain circuit integrity under fire conditions)。BS6387 CWZ级别耐火测试需要通过火焰燃烧测试,水喷淋测试和机械冲击震动燃烧测试。详细内容请咨询南京睿督公司咨询电话:025-8658 3475。

英标耐火电缆标准-BS6387耐火冲击水喷完整性测试
全球通用的耐火电缆标准的着眼点是依赖电缆绝缘保持其在火灾条件下完整性的能力。英国标准BS6387“在火灾条件下保持线路完整性的电缆性能要求”提出了一些衡量不同火焰温度、喷水和机械冲击条件下电缆性能的判据。这个被称为“CWZ”的最高级别的标准,即耐火电缆耐火性能分类试验标准,是目前世界上耐火电缆的最高标准。这个标准的具体试验要求是:

英国BS6387 C类耐火电缆:经受950℃火焰烧180分钟;
英国BS6387 W类耐火电缆:经受650℃火焰烧15分钟和喷水浇15分钟;
英国BS6387 Z类耐火电缆:经受950℃火焰烧和机械冲击15分钟。
本标准的目的为评估当电缆暴露在这些情况下,电缆是否能够电路的完整性。这对于消防安全系统非常重要,如应急照明场所。耐火电缆国外测试标准主要有:BS8491,BS6387,BS EN 50200,BS 8491等标准。

南京睿督公司全国免费咨询电话:400-603-6575   025-8658 3475
网址:www.fire-test.com    www.fire-test.cn
邮箱:info@fire-test.com
 

地址:江苏省南京市建邺区江东中路118号德盈大厦1622
电话:025-8658 3475
传真:025-8658 3457
网址:http://www.bs6853.com/
邮箱:info@fire-test.com

脚注信息
版权所有 Copyright(C)2012-2015  南京睿督科技有限公司 版权所有  苏公网安备 32010502010099号    备案号:苏ICP备10201999号-9
图片